IJV Volume 5 No 2 Contents

 
Paper 5:  Volume 5 No.2 Sept 2006 Edition

Comparative Energy Analysis of a Constant Air Volume (CAV) System and a Variable Air Volume (VAV) System for a Software Laboratory

Kalaiselvam. S1, Vidhya sagar Velichet.1, Iniyan. S1 and Anand A. Samuel2

1Refrigeration and Air Conditioning Division, Department of Mechanical Engineering,
Anna University , Chennai , India .

2President, ISHRAE Chennai chapter,
Vellore Institute of Technology, Deemed University, Vellore , India  

Buy paper for email delivery
Credit Card or PayPal

  Abstract

The objective of heating, ventilating and air conditioning (HVAC) systems is to satisfy users when it comes to health, indoor air quality (IAQ), and thermal comfort. Air conditioning systems employed to provide thermal comfort and indoor air quality consume a significant part of building energy requirements. Any effort to minimise energy consumption improves cost effectiveness and economics. A variable air volume (VAV) system is a choice in that direction. In this research, a relative energy consumption analysis of a constant air volume (CAV) system and VAV system has been performed. For the purpose of this study, a software laboratory was taken and the load pattern was determined. For the derived load pattern an energy analysis of major components of the HVAC system was carried out. It was found that energy savings in the chiller varied from 14 % to 20 % and that fan energy savings were between 20 % and 48 %. To meet indoor air quality (IAQ) requirements a ventilation strategy based on air quality demand control ventilation (DCV) was evaluated. This took into account the contaminants generated from both human and other sources such as the building and equipment, etc.

Key words:  variable air volume (VAV), demand control ventilation (DCV), energy savings, indoor air quality, thermal comfort, HVAC component energy analysis, variable occupancy.

References

Ameen A and Mahmud K: (2005) “Energy performances of prototype VAV and CAV systems under simulated humid tropical climates”, ASHRAE Transactions, pp320-327.

ASHRAE: (1999) ANSI/ASHRAE Standard 62-1999 “Ventilation for Acceptable Indoor Air Quality”, American Society of Heating Refrigerating and Air Conditioning Engineers, Atlanta , GA.

EPA: (1991) “Office of Air and Radiation Indoor Air Facts No. 4: Sick Building Syndrome”. Environmental Protection Agency , U.S.

Engdahl F and Johansson D: (2004) “Optimal supply air temperature use with respect to energy use in a variable air volume system”, Energy and Buildings, (36), pp 205-218.

Sauer HJ and Howell RH: (1992) “Estimating the indoor air quality and energy performance of VAV systems”, ASHRAE Journal, pp 43-50.

Moncef K and Alawi MAL: (2004) “Analysis of the impact of CO2 based Demand- Controlled Ventilation Strategies on Energy Consumption”, ASHRAE Transactions, pp 274-286.

Mumma SA and Bolin RJ: (1997) “Energy optimized ventilation constrained variable air volume system control”, Automation in Construction, (6), pp 463-471.

Mumma SA and Yu-Pei Ke: (1997) “Using carbon dioxide measurements to determine occupancy for ventilation controls”, ASHRAE Transactions, pp 365-374.

Reddy TA, Liu M and Claridge DE : (1998) “A study of energy use and satisfactory zone ventilation of different outdoor air ventilation strategies terminal reheat variable air volume systems”, Energy and Buildings, (29), pp 65-75.

Sekhar SC : (1997) “A critical evaluation of variable air volume system in hot and humid climates”, Energy and Buildings, (26) pp223-232.

Wang S and Xu X: (2004) “Optimal and robust control of outdoor ventilation air flow rate for improving energy efficiency and IAQ”, Building and Environment, (39), pp763-773.

Inoue U and Matsuomoto T: (1979) “A study on energy savings with variable air volume systems by simulation and field measurement”, Energy and Buildings, pp27-36.

Yiquan P, Zhou H, Huang Z, Zeng Y and Long W: (2003) “Measurement and simulation of indoor air quality and energy consumption in two Shangai office buildings with variable air volume systems”, Energy and Buildings, (35) pp877-891.

 

 